RELEQUICK •• ELECTRONIC MODULES FOR THE INDUSTRIAL AUTOMATION Español  •   Deutsch  •   Français
OUR PRODUCTS Phase controlling module
Relequick's digital module for current control
Phase control module

This electronic digital programmable relay has been specially designed to monitor the voltage asymmetry, sequence and loss phase of a three-phase power system.

The module is designed to be mounted on Din-rail and it let to monitor all the power specifications and topologies that exist on the world.                
With its compact design (22.5mm wide casing) it can be mounted on a DIN rail.

Technical features
Download datasheet
    The module can be programmed in two ways:
        • Manual mode: adjust the percentage values ​​of asymmetry and time delay by potentiometers and power specifications and topologies through switches
        • Programming mode: thanks to a built-in mini-USB port will be able to connect the module to a PC. With Our Devices Programmer software it is possible to program easily different percentage values ​​of asymmetry and time delay besides the power specifications and topologies that exist on the world.
Software security lock of the manual regulated range.
Monitoring of asymmetry power, correct sequence and phase loss with signs of status, alarm and LED power up.
Compact design, easy wiring and 22.5mm wide casing.
LED signaling alarm output on the front side.
One output relay SPDT with switching capacity of 6A, 250VAC/30VDC.

Two models cover all the voltage range, with direct multivoltage supply. Versions with one and two output relays are available for both models:

Mod:

 

  • MCP240: 200-240VAC
  • MCP480: 380-480VAC
Connection diagram, functions and installation information laser-marked.
Certifications: CE, UL.
Uses and applications

The asymmetry, correct sequence and phase loss monitoring has great applications in industry, buildings and all kinds of installations, both in loads monitoring, as in the protection of machines or small installations.

 

Mainly used to prevent malfunction of three phase motors in which an imbalance of the asymmetry, the loss of one phase or the inverse power can cause damage or overheating the machine.


Examples: pumps, compressors, forklifts, generators, etc.

Functions table

Function 0

Factory default. Normal operating mode in which the function of asymmetry is set with the potentiometers and the type of topology of the three-phase power supply is set with the DIP switch.

Ranges: Voltage from 200VAC to 240VAC in the  MCP240 model and from 380VAC to 480VAC in the MCP480  model and  delay time(Lock) from 0.1 seconds to 30 seconds
Function0

Function 1

If asymmetry occurs, the alarm LED flashes until the status relay LED turn off (Lock), after which time, the alarm LED will remain lit.
Once the symmetry recovers the alarm LED will turn off and after a time (t1), the status relay LED will remain lit.
Programmable delay time relay output of 0 to 999 seconds (Lock and T1). Parameters will be set by the user using the Devices Programmer software.
In this case, one can activate or deactivate the potentiometers and the DIP switch using the Easy Control Programmer software. If activation is selected, potentiometers must be set at minimum. If this setting is changed, the settings can be configuring manually again.
If the potentiometers and DIPs are locked, the asymmetry and three-phase power specifications cannot be changed manually.

function1
References
MCP240 From 220 VAC to 240 VAC voltages.
MCP480 From 380 VAC to 480 VAC voltages.
Connection diagrams
Connection
Front side
Front view of the current control module
Dimensions
Dimensions

Valid XHTML 1.0 Transitional ISO 9001 certified