RELEQUICK •• SOLID STATE RELAYS FOR THE INDUSTRIAL AUTOMATION Español  •   Deutsch
OUR PRODUCTS Three phase SSR - AC load & zero crossing
Relequick's zero crossing AC SSR
Features
Download datasheet
  • Three phase AC solid state relay, zero crossing
  • 2 input ranges: 3 - 32 VDC and 90 - 250 VAC
  • Maximum load current (AC1 at 25° C): 25, 60, 80, 100, 120 A
  • Operational ratings: 40 - 530 VAC
  • Frequency range: 47 - 63 Hz
  • Maximum non-repetitive peak voltage: 1,000 Vp
  • LED indicator
  • Clip on protective cover for greater safety (IP 20)
Models and references
Zero crossing Control voltage Rated operational voltage Rated operational current Reference
Yes 3 - 32 VDC 40 - 440 VAC 25 A RS3A0P032DC440025Z
60 A RS3A0P032DC440060Z
80 A RS3A0P032DC440080Z
120 A RS3A0P032DC480120Z
90 - 250 VAC 25 A RS3A0P250AC440025Z
60 A RS3A0P250AC440060Z
80 A RS3A0P250AC440080Z
40 - 530 VAC 100 A RS3A0P280AC480100Z
General specifications
  VDC input VAC input
Dielectric insulation (between input and output) 2,500 VAC 2,000 VAC
Operating temperature -25 to 70° C -40 to 80° C
Storage temperature -35 to 85° C -45 to 85° C
Operating ambient humidity Up to 85 %
CE marking Yes
Input specifications
  VDC input VAC input
Control voltage range 3 - 32 VDC 90 - 250 VAC
Maximum input current 5/25 mA @= 3 V / 32 V 5/30 mA @= 90 VAC / 250 VAC 15/20 mA @= 90 VAC / 250 VAC (only RS3A0P250AC530100Z)
Pick-up voltage 3 VDC 70 VAC
Drop-out voltage 1 VDC 70 VAC
Maximum reverse voltage 32 VDC -
Maximum response time pick-up 10 ms
Maximum response time drop-out 10 ms
Output specifications
  VDC input VAC input
Maximum load current        
      (AC51 @ Ta = 25° C) 25, 60, 80 A 120 A 25, 60, 80 A 100 A
      (AC53a @ Ta = 25° C) 5, 15, 18 A 21 A 5, 15, 18 A 20 A
Load voltage range 40 - 440 VAC 40 - 530 VAC
Frequency range 50 - 60 Hz 47 - 63 Hz
Maximum non-repetitive peak voltage 930 Vp 1,000 Vp
Maximum non-repetitive peak current (t = 10 ms) 350 Ap / 25 A 1,400 Ap 350 Ap / 25 A 1,100 Ap
630 Ap / 60 A 630 Ap / 60 A
910 Ap / 80 A 910 Ap / 80 A
Maximum off state leakage current 10 mA 1 mA
Maximum on state voltage 1.6 VAC 1.5 VAC
Minimum off state dv / dt 300 V / µs
Minimum load current 0.1 Arms
I2t (10 ms) (orientative data) 625 A2s (25 A)
2,025 A2s (60 A)
4,225 A2s (80 A)
6,050 A2s (100 A)
9,800 A2s (120 A)
Housing specifications
  VDC input VAC input
Dimensions (L x W x H mm) 105 x 75 x 32 120 x 85 x 50
Weight 500 g maximum
Baseplate Aluminum, nickel-plated
Control terminal (M3x6) torque 1.2 Nm
Power terminal (M5x9) torque 2.4 Nm
Dimensions
Dimensions of Relequick's three phase SSR
Load current vs. ambient temperature
Input voltage vs. output voltage Input current vs. output voltage
Input voltage vs. output voltage Input current vs. output voltage
Input voltage vs. output voltage  
Heat sinks
Heat sink reference Output current Dimensions (mm) Relays to be used with
RSH-035 ≤ 20 A 150 x 90 x 35 RS3A0P032DC440025Z
RS3A0P250AC440025Z
RSH-036 ≤ 40 A 150 x 100 x 80 RS3A0P032DC440025Z
RS3A0P250AC440025Z
RSH-037 ≤ 80 A 260 x 180 x 50 RS3A0P032DC440060Z
RS3A0P250AC440060Z
RSH-038 ≤ 100 A 150 x 125 x 135 RS3A0P032DC440080Z
RS3A0P250AC440080Z
RS3A0P250AC530100Z
RSH-039 ≤ 200 A 200 x 125 x 135 RS3A0P032DC440120Z

Valid XHTML 1.0 Transitional ISO 9001 certified